The Conext TL inverter supports the Modbus communication protocol via an RS485 interface. Both an RJ-45 and terminal block wiring interface are supported. The module also provides an RID (Remote Inverter Disable) input and a dry (not energized) contact for signaling purposes.

RS485 Communication Parameters
Parameters Value Parameters Value
Baud Rate 9600 Stop bits 1
Data Bits 8 Parity None

Via RJ45

Data Pin 4 Data +
Pin 5 Data –
Power Pin 7 Not Connected
Pin 8 Modbus Ground

connect trackso with schneider electric solar inverter via  RS485 / RS232/ RJ45 port for remote monitoring via IOT Platform

Data

Pin 1

TrackSo Data +

Pin 2

TrackSo Data –

Power

Pin 3

Chassis Ground

Pin 4

Modbus Ground

Pin 5

Not Connected